Secondary Voltage Fuse Blown
Quick Answer
Error code 24 on your Carrier Central Air Conditioners & Furnaces means: Secondary Voltage Fuse Blown. This is usually fixable — see the step-by-step guide below.
Affected Models
Likely Causes
  1. Short circuit in thermostat wiring (common with rodent damage)
  2. Shorted contactor coil in outdoor unit
  3. Miswired thermostat or accessories drawing excessive current
  4. Failed transformer secondary winding
How to Fix It
1
Locate and check the 3-amp or 5-amp fuse on the control board
2
Disconnect all thermostat wires and check for shorts between conductors
3
Check transformer output voltage (should be 24-28VAC with no load)
4
Inspect outdoor unit contactor coil for short circuit
5
Reconnect wires one at a time to isolate the shorted circuit
Pro Tip
This fix requires some technical knowledge. If you're unsure about any step, consider contacting support or a qualified technician.
Parts You May Need
Automotive-style 3A or 5A fuse
24V transformer
Thermostat wire