C
32
Moderate
Carrier · Central Air Conditioners & Furnaces
Limit Circuit Fault
Quick Answer
Error code 32 on your Carrier Central Air Conditioners & Furnaces means: Limit Circuit Fault. This is usually fixable — see the step-by-step guide below.
Likely Causes
  1. Airflow restriction causing overheating
  2. Dirty air filter or blocked return air duct
  3. Blower motor not reaching proper speed
  4. Failed run capacitor on blower motor
How to Fix It
1
Check and replace the air filter
2
Verify all supply and return registers are open
3
Measure blower motor amperage and compare to nameplate rating
4
Test blower motor run capacitor with a multimeter (should be within 5% of rated microfarads)
5
Check temperature rise across the heat exchanger (should match nameplate range)
Pro Tip
This fix requires some technical knowledge. If you're unsure about any step, consider contacting support or a qualified technician.
Parts You May Need
Air filter
Blower motor run capacitor
High-limit switch