Daikin · Mini-Splits & Ductless Systems
Compressor Overload Protection
Quick Answer
Error code E5 on your Daikin Mini-Splits & Ductless Systems means: Compressor Overload Protection. This is usually fixable — see the step-by-step guide below.
Likely Causes
  1. Compressor drawing excessive current due to mechanical wear
  2. Low voltage at the outdoor unit power supply
  3. Failed compressor start capacitor
  4. High ambient temperature combined with dirty condenser
How to Fix It
1
Measure compressor amperage with a clamp meter and compare to the rated load amps on the nameplate
2
Check voltage at the outdoor unit disconnect (must be within 10% of rated voltage)
3
Inspect and test the compressor start components (capacitor, relay)
4
Clean the condenser coil to improve heat rejection and reduce compressor load
5
If compressor amperage consistently exceeds RLA, compressor replacement by a licensed technician is required
Pro Tip
This fix requires some technical knowledge. If you're unsure about any step, consider contacting support or a qualified technician.
Parts You May Need
Compressor start capacitor
Compressor (if failed)
Hard start kit