Y
e3
Moderate
York · HVAC Systems (AC, Furnaces, Heat Pumps & Thermostats)
Compressor Overcurrent
Quick Answer
Error code E3 on your York HVAC Systems (AC, Furnaces, Heat Pumps & Thermostats) means: Compressor Overcurrent. This is usually fixable — see the step-by-step guide below.
Likely Causes
  1. Compressor drawing excessive amperage due to mechanical wear
  2. Low supply voltage to the outdoor unit causing higher current draw
  3. Failed compressor capacitor causing hard starts
  4. Compressor winding insulation beginning to break down
How to Fix It
1
Measure compressor running amperage with a clamp meter and compare to the nameplate RLA
2
Check voltage at the outdoor unit disconnect under compressor load (should be within 10% of rated voltage)
3
Test the compressor run capacitor with a capacitance meter (should be within 5% of rated value)
4
Inspect the compressor terminal connections for signs of overheating or arcing
5
If the compressor consistently exceeds RLA, a licensed HVAC technician should evaluate for compressor replacement
Pro Tip
This fix requires some technical knowledge. If you're unsure about any step, consider contacting support or a qualified technician.
Parts You May Need
Compressor run capacitor
Hard start kit
Contactor
Compressor (if failed)
Related Error Codes
Video Guides
Loading video guides…
Search more on YouTube →