Y
e6
Moderate
York · HVAC Systems (AC, Furnaces, Heat Pumps & Thermostats)
Indoor Coil Temperature Sensor Fault
Quick Answer
Error code E6 on your York HVAC Systems (AC, Furnaces, Heat Pumps & Thermostats) means: Indoor Coil Temperature Sensor Fault. This is usually fixable — see the step-by-step guide below.
Likely Causes
  1. Indoor coil thermistor disconnected or reading out of range
  2. Sensor wire damaged during installation or service
  3. Sensor physically displaced from the evaporator coil
  4. Corroded connector at the indoor unit control board
How to Fix It
1
Locate the indoor coil thermistor on the evaporator coil surface
2
Measure the thermistor resistance and compare to the manufacturer's chart
3
Verify the sensor is properly mounted to the coil with good thermal contact
4
Check the wiring and connector at the indoor control board for corrosion
5
Replace the sensor if resistance is out of the expected range
Pro Tip
This fix requires some technical knowledge. If you're unsure about any step, consider contacting support or a qualified technician.
Parts You May Need
Indoor coil thermistor
Sensor mounting clip
Wire connectors