Y
e8
Moderate
York · HVAC Systems (AC, Furnaces, Heat Pumps & Thermostats)
Outdoor Fan Motor Error
Quick Answer
Error code E8 on your York HVAC Systems (AC, Furnaces, Heat Pumps & Thermostats) means: Outdoor Fan Motor Error. This is usually fixable — see the step-by-step guide below.
Likely Causes
  1. Outdoor fan motor winding failure
  2. Fan motor capacitor failed
  3. Fan blade physically obstructed by debris or ice
  4. Loose or corroded motor connector at the outdoor board
  5. Fan motor bearings seized
How to Fix It
1
Inspect the outdoor fan blade for damage or obstructions preventing rotation
2
With power off, spin the fan blade by hand to check for free rotation and bearing condition
3
Test the fan motor capacitor with a capacitance meter (should be within 5% of rated value)
4
Check the motor connector at the outdoor board for corrosion or loose pins
5
Measure fan motor winding resistance across each pair of leads and compare to specifications
Pro Tip
This fix requires some technical knowledge. If you're unsure about any step, consider contacting support or a qualified technician.
Parts You May Need
Outdoor fan motor
Fan motor capacitor
Fan blade
Motor mounting hardware