7 flashes
Moderate
Goodman · HVAC Systems (AC, Furnaces & Heat Pumps)
Gas Valve Fault
Quick Answer
Error code 7 flashes on your Goodman HVAC Systems (AC, Furnaces & Heat Pumps) means: Gas Valve Fault. This is usually fixable — see the step-by-step guide below.
Likely Causes
  1. Gas valve coil winding open or shorted
  2. Wiring fault between the control board and gas valve
  3. Control board gas valve output circuit failure
  4. Incompatible gas valve replacement installed
How to Fix It
1
Measure gas valve coil resistance across the terminals (typically 150-600 ohms depending on model)
2
Verify 24VAC is present at the gas valve leads during a call for heat
3
Check wiring continuity from the control board to the gas valve connector
4
Verify the correct gas valve part number for the specific furnace model
5
Gas valve replacement involves gas piping and must be done by a licensed HVAC technician
Pro Tip
This fix requires some technical knowledge. If you're unsure about any step, consider contacting support or a qualified technician.
Parts You May Need
Gas valve assembly
Control board
Wiring harness