L
211
Moderate
Lennox · HVAC Systems (AC, Furnaces & Heat Pumps)
Ignition Failure
Quick Answer
Error code 211 on your Lennox HVAC Systems (AC, Furnaces & Heat Pumps) means: Ignition Failure. This is usually fixable — see the step-by-step guide below.
Likely Causes
  1. Failed hot surface igniter (cracked or open circuit)
  2. Gas supply turned off or insufficient gas pressure
  3. Defective gas valve not opening when commanded
  4. Dirty or misaligned burner orifices
  5. Control board ignition circuit malfunction
How to Fix It
1
Check gas supply valve is in the ON position
2
Remove the igniter and measure resistance (silicon nitride: 40-200 ohms; silicon carbide: 40-75 ohms)
3
Visually inspect the igniter for hairline cracks or white discoloration
4
Verify 120VAC is present at the igniter terminals during the ignition sequence using a multimeter
5
Check gas manifold pressure with a manometer (3.5 in WC for natural gas, 10.0 in WC for LP)
Pro Tip
This fix requires some technical knowledge. If you're unsure about any step, consider contacting support or a qualified technician.
Parts You May Need
Hot surface igniter
Gas valve
Igniter mounting gasket